TLS-450 Setup and Operation Screens Manual
245
Threshold
Value range: 0.00 to 9.99 gal (0.00 to 37.82L)
Start Volume
Value range: 0 to 264,172 gal (0 to 999,999L)
Fuel Height
Value range: 0 to 390.0 in. (0 to 9906.0mm)
Percent Volume
Value range: 0.0 to 100.0
Water Height
Value range: 0 to 390.0 in. (0 to 9906.0mm)
Cumulative Periodic Volume Change
There is one Cumulative Periodic Volume Change field for each completed one half hour of test duration,
up to 47 fields maximum. The fields will be displayed in rows of ten fields maximum.
Value range: -26.41 to 26.41 gal (-99.99 to 99.99L)
SLD Test In-Progress Report Refresh Rate
The SLD Test In-Progress Report data will be refreshed every 30 seconds.
Test Control Buttons (on right of screen)
Setup
Touch this button to open the Tank Setup - SLD Test Setup screen.
Manual Test
Touch this button to open the Manual Static Leak Detect screen to start or stop a SLD test.
Regulatory Compliance
Note: In-tank leak tests will not be declared a PASS unless the product level in the tank satisfies the
minimum product level defined in our Third Party certification for the leak test being performed. In-tank
leak tests performed with the product level below these minimum levels will be declared Invalid. Because
the minimum product level requirements vary with local, state, and federal regulations, you need to
ensure that the product level complies with the applicable regulations in your location.