![Veeder-Root TLS-450 Setup And Operation Download Page 336](http://html2.mh-extra.com/html/veeder-root/tls-450/tls-450_setup-and-operation_3793936336.webp)
TLS-450 Setup and Operation Screens Manual
325
Status Message
Possible messages include:
•
Insufficient data collection rate
- Warning will be posted when the average number of records
generated per day is less than N, and the throughput is below a threshold T.
•
Noisy data
- Warning will be posted after a calibration is generated, and the RMS Error of the
data exceeds a threshold T.
•
Data too regionally concentrated
- Warning will be posted after N records are generated over
time T, and the data sufficiency is less than the current threshold.
•
Initial tank parameters suspicious
- Warning will be posted after a calibration is generated, and
the search algorithm hits a boundary.
•
Station too busy
- Warning will be posted when the average number of records generated per
day is less than N, and the throughput is above a threshold T.
•
No Successful Calibration Has Happened
- Warning will be posted after a calibration should
have been generated, but the algorithm was unable to generate a calibration. When you try to
clear the warning, you will be prompted to extend, terminate, or restart the calibration
period. Selecting any of these options will clear this warning.
•
Calibration done, quality validation required
- Warning will be posted after a calibration is
generated, but the quality of the calibration is low. When you try to clear the warning, you will be
prompted to extend, terminate, or restart the calibration period. Selecting any of these options
will clear this warning.