Device Setup - Mag Sensor
This screen allows you to setup Mag Sensors connected to the console. The Mag Sensor defines the
fields that are available for editing, the ranges for each field, and the default value. The Mag Sensor
cannot be setup until its device address has been assigned.
If your console has the internal printer, touch the Print button to printout the Mag Sensor Setup. On the
printout, look at the factory preset Alarm Delay and Alarm Threshold settings for the Mag Sensor (see
Mag Sensor setup printout example below):
MAG SENSOR ALM DELAY
SENSOR LABEL DELAY
1 (label) 48
MAG SENSOR ALARM THRESHOLD
MS 1:(label)
ID VALUE THRESHOLD ALARM PROGRAMMBLE UPGRADE
1 FUEL HT > 1.6 FUEL ALARM NO NO
3 WATER HT > 3.0 WATER ALARM NO NO
4 WATER HT > 1.7 WATER WARNING NO YES