![Veeder-Root TLS-450 Setup And Operation Download Page 116](http://html2.mh-extra.com/html/veeder-root/tls-450/tls-450_setup-and-operation_3793936116.webp)
TLS-450 Setup and Operation Screens Manual
105
Allowable selections: None, PLLD. Default: None
Pressure Sensor
Allowable selections: Choose from drop-down list of available sensors (you should pick the pressure
sensor assigned to this line), Not Assigned. Default: Not Assigned
Manifolded
Allowable selections: Yes, No. Default: No
Dispense Mode
This field is disabled for edit unless the Manifolded field is set to "Yes". For non-manifolded lines, the
dispense mode is set to Standard by default. If the mode selected in pump setup was TLS Pump Control
then all options are available and the default is Standard. Otherwise for other modes selected in pump
setup, the only option for dispense mode is Standard.
Options for dispense mode are:
•
Standard - Typically this means that only one pump feeds the line. However if the selected pump
mode is External Pump Control this is not the case since the console is not controlling the
actuator/control for the pump.
•
Alternate - If there is more than one tank with a pump on the line, the console will actuate the
pump to run the tank with the greatest inventory volume.
•
Sequential - If there is more than one tank with a pump on the line, tanks are pumped low one at
a time until volume drops below pump threshold percentage. At that point pumping will
commence on the next available tank in the line set.
•
All - All pumps on the line are run.
Pumps
A multi-select list of pumps will be provided for picking the pumps you can assign to the selected
line. The multi-select drop down list for this field will contain pumps defined in the console that are both
configured and non-configured and include those that have been assigned to the selected line plus those
that have not been assigned to any line. The pumps that are assigned to the current line will be
highlighted. The pumps that are not configured will be prefixed with a "!" symbol to distinguish them from
the rest. After all pumps have been selected for the set, they will be displayed in the Pumps field
separated by a colon (:).
Pumps selected for a line should have the same pump mode setting or an error message box will be
shown describing why the selected pump cannot be added to the list.
The maximum number of pumps that can be added to a single line is 8.
Allowable selections: Choose from drop-down list of available pumps, Not Assigned
Default: Not Assigned