TLS-450 Setup and Operation Screens Manual
249
Hours
Value range: 0.0 to 24.0 (blank for Gross test)
Leak Rate
Value range: -26.42 to 26.42 gal/hour (-99.99 to 99.99L/hour)
Tank Volume
Value range: 0 to 264,172gal (0 to 999,999L)
%Volume
Value range: 0.0 to 100.0
SLD History Report Refresh Rate
The SLD History Report data will be refreshed every 30 seconds.
Control Buttons (right of screen)
Setup
Touch this button to open the Tank Setup - SLD Test Setup screen
Manual Test
Touch this button to access the Manual Static Leak Detect screen in which you can start a SLD test.
Select Range
Touch this button to setup the report's contents:
•
Select Option List
- Select data for report: All Records, Day, Week, Month, Year, Date Range
•
Period Option List
- Select period: Previous, Previous n selections
•
Select Tank(s)
- Select tank(s) to report: "All Tanks" or "Current Tank"
Regulatory Compliance
Note: In-tank leak tests will not be declared a PASS unless the product level in the tank satisfies the
minimum product level defined in our Third Party certification for the leak test being performed. In-tank
leak tests performed with the product level below these minimum levels will be declared Invalid. Because
the minimum product level requirements vary with local, state, and federal regulations, you need to
ensure that the product level complies with the applicable regulations in your location.