5-15
5
System Setup
Precision Test Duration (PLLD/WPLLD Only)
Press STEP to display the message:
This option allows either Tank Height or Tank Volume data for H-protocol. On power up, this feature will default to
HEIGHT for backward compatibility. Press CHANGE, then ENTER to change the default. Accept the default if you
are not using H-protocol.
Precision Test Duration
(PLLD/WPLLD Only)
When optional 0.2 gph (0.76 lph) [PLLD and WPLLD] and 0.1 gph (0.38 lph) [PLLD only] line leak tests are
enabled, this feature lets you extend the time between a passed test and running the next test from 12 hours (60
hours with CSLD option), up to a maximum of 744 hours (31 days).
Press STEP to display the message:
Press CHANGE, then enter the desired duration (from 12 up to 744 hours without the CSLD option, or from 60
up to 744 hours with the CSLD option), then press ENTER.
Precision Line Test Auto-Confirm
These Auto-Confirm selections reduce the risks of false 0.2 and 0.1 gph (0.76 and 0.38 lph) line test results.
However, enabling these options extends the time it takes to post line test results.
Press STEP to display the message:
This feature evaluates several individual 0.2 gph line tests before a result is posted. To leave Auto-Confirm
enabled, press STEP: To disable Auto-Confirm, press CHANGE, ENTER.
Press STEP to display the message:
This feature evaluates several individual 0.1 gph line tests before a result is posted. To leave Auto-Confirm
enabled, press STEP: To disable Auto-Confirm, press CHANGE, ENTER.
Press STEP to display the message:
To leave the printing of 0.2 and 0.1 gph test results disabled, press STEP: To enable these printouts, press
CHANGE, ENTER.
H-PROTOCOL DATA FORMAT
HEIGHT
PRECISION TEST DURATION
HOURS: XXX
0.2 GPH LINE TEST
AUTO-CONFIRM: ENABLED
0.1 GPH LINE TEST
AUTO-CONFIRM: ENABLED
PRINT PRECISION LINE
TEST RESULTS: DISABLED