7-13
7
In-Tank Setup
Float Size
•
Entering a Tank Tilt value is not recommended if the system is performing automatic Business Inventory
Reconciliation and AccuChart.
Calibration Update Selections
To change the method for calibration updates, press CHANGE until the desired method appears. Descriptions of
the available update methods are listed below.
•
Immediate
--This method provides the most accurate reconciliation results. It is designed for customers using
BIR reports for reconciliation. All calibrations and any resulting changes in product volume go into effect
immediately, as they occur. Changes to the product volume will not generate BIR variance errors.
•
Periodic
--This method is designed for customers performing manual reconciliation. It allows a maximum of two
changes to product volume, as a result of AccuChart’s calibration. The first calibration update occurs 28 days
from the startup of AccuChart and the second calibration update occurs 56 days from the startup of AccuChart.
•
Complete
--This method is also designed for customers performing manual reconciliation. It is similar to the
Periodic method, except that it allows only one change to product volume, as a result of AccuChart’s calibration.
The only calibration update occurs 56 days from the startup of AccuChart.
•
Never
--This setting is used by customers who want to disable AccuChart (two reasons are discussed below).
Height to volume calculations are performed by using the values entered by the customer for diameter, tilt, and
capacity. If the customer changes the method from
Never
to one of the other methods, the other method goes
into effect immediately.
1. For PLLD installations with line manifolded tanks, the master tank’s check valve’s relief pressure must be
below the pump’s operating pressure. AccuChart will run when there is line manifolding with PLLD line leak
detection; however, you should disable AccuChart if the results are poor.
2. AccuChart also cannot support ISTs if they are communicating to each other. The same is true of Red
Jacket’s CPT and any other configuration where all pumps are On (e.g., Dispensing mode = All [see page 10-7,
page 11-6, or page 15-2 as appropriate]). Disconnecting the ISTs/CPTs links and/or selecting Sequential or
Alternate dispense modes during the calibration period would overcome this limitation.
Press ENTER to confirm your choice. Press STEP to continue.
Float Size
This display requires that you enter the installed Mag probe float size.
Enter the float size installed on the tank’s probe: 4-, 3-, 2-, or 1-inch (101 mm, 76 mm, 50 mm, or 25 mm), 4.0 IN.
PS or Custom. The system automatically recognizes which Mag probe type you have installed and will display only
the applicable float size options. Only select "Custom" if the literature that was shipped with the float specifically
states that you must choose this float size selection, i.e., Chem-ISO and LPG-ISO probes. The installation
literature accompanying Chem-ISO and LPG-ISO probes will list the required values to enter.
Press CHANGE to display the float size you installed (for Custom, see literature accompanying float), then press
ENTER to confirm your choice. Press STEP to continue.
T1: (Product Label)
FLOAT SIZE: 3.0 IN.