7-23
7
In-Tank Setup
Periodic Test Fail
Annual Test Fail alarms when an annual leak test has not passed. You can enable or disable this alarm. To disable
the alarm, press STEP. (The system displays the PERIODIC TEST FAIL message.) To enable the alarm for the
selected tank, press CHANGE and press ENTER. The system displays the message:
Periodic Test Fail
If necessary, press STEP until you see the message:
The Periodic Test Fail feature allows you to disable or enable an alarm that triggers if a 0.2 gph (0.76 lph) leak test
fails. To disable the alarm, press STEP. (The system displays the GROSS TEST FAIL message.) To enable the
alarm for the selected tank, press CHANGE and press ENTER. The system displays the message:
Gross Test Fail
If necessary, press STEP until you see the message:
The Gross Test Fail feature allows you to disable or enable an alarm that triggers when a 3.0 gph (11.3 lph) leak
test fails. To disable the alarm, press STEP. (The system displays the ANN TEST AVERAGING message.) To
enable the alarm for the selected tank, press CHANGE and press ENTER. The system displays the message:
Annual Test Averaging
If necessary, press STEP until you see the message:
When on, Annual Test Averaging averages the last ten 0.1 gph (0.38 lph) in-tank leak tests. To leave the feature
off, press STEP. (The system displays the PER TEST AVERAGING message.) To turn on the feature, press
CHANGE and press ENTER. The system displays the message:
ALARM ENABLED
PRESS <STEP> TO CONTINUE
T1: PERIODIC TEST FAIL
ALARM DISABLED
ALARM ENABLED
PRESS <STEP> TO CONTINUE
T1: GROSS TEST FAIL
ALARM DISABLED
ALARM ENABLED
PRESS <STEP> TO CONTINUE
T1: (product Label)
ANN TEST AVERAGING: OFF
ANN TEST AVERAGING: ON
PRESS <STEP> TO CONTINUE