Pressurized Line Leak Detection
Piping Type
10-2
When the appropriate PLLD appears in the display, press CHANGE. (To erase a label press CHANGE again.)
Enter up to 20 alphanumeric characters for the line label and press ENTER. The system confirms your entry with
the message:
Press STEP to continue.
Piping Type
This display allows you to select the type of line being used:
• 2.0 IN. (50 mm) STEEL
•
2.0/3.0 IN. (50/76 mm) FIBERGLASS
• 1.5 (38 mm) IN. ENVIRN GFLEXII
• ENVIROFLEX PP1501
•
ENVIROFLEX PP1500
• WFG COFLX2000 RIBBED
• OMNIFLEX CP1501
•
1.5/2 IN. ENVIRON GFLXD
• ENVROFLX PP1503/2503
• ENVROFLX PP1502/2502
•
OPW PISCES SP15
• OMNIFLEX CP1503
• OPW PISCES CP15
•
APT P175SC
• OPW PISCES CP15DW
• OPW PISCES CP20
•
USER DEFINED*
• PETROTECHNIK UPP EXTRA 63 MM
• OPW PISCES SP20
* To select ‘User Defined’, you must know the Bulk Modulus of the pipe type.
IMPORTANT! To ensure accurate line monitoring, you must enter the piping type that is installed for this line. The
default is Enviroflex PP1501.
Press CHANGE, enter the correct pipe type, press ENTER to confirm your choice and continue.
Piping Length
This display allows you to enter the total length of piping run between the tank and the dispensers. For manifolded
tanks, include the length of piping between the manifolded tank’s check valve and where it connects into the
product line.
NOTE: Refer to the Veeder-Root Line Leak Application Guide (Part No. 577013-465) for approved minimum and
maximum piping lengths.
IMPORTANT! The default line length must be changed to reflect the actual line length or a Setup Data Warning
will occur.
Press STEP until you see the message:
Press CHANGE, enter the actual line length (rounded up to the next foot or meter). Press ENTER to confirm your
choice and press STEP to continue.
Q1: (Pressure Line Label)
PRESS <STEP> TO CONTINUE
Q1: (Pressure Line Label)
TYP: ENVIROFLEX PP1501
Q1: (Pressure Line Label)
LINE LENGTH: XXX