13
Volumetric Line Leak Tests
Leak Test Frequency
13-2
Leak Test Frequency
As mentioned, when you select a leak test method—ALL LINES in this example—the system displays the message:
You can now choose to run the line leak tests on a specific date, or you can run the tests on an annual, monthly,
weekly, or daily basis.
ON DATE
To run the test on a specific date, press STEP in response to the ON DATE message. (To run the test annually,
monthly, weekly, or daily, follow the procedures described in the appropriate section below.) The system displays
the message:
Press CHANGE, and enter the date on which you want the tests to run. Enter the date in the format MM/DD/
YYYY. Press ENTER to confirm the date:
Press STEP to continue. The system displays the START TIME message. Follow the procedure under “Leak Test
Start Time” on page 13-4.
ANNUAL TEST
To run the tests annually, press CHANGE and press ENTER in response to the ON DATE message:
The system displays the message:
Press STEP to continue setting the annual test. The system displays the message:
To set the date of the annual test, press CHANGE until the month during which you want to perform the test
appears, and press the Right Arrow key. Press CHANGE until the week during which you want to perform the test
appears and press the Right Arrow key. Press CHANGE until the day on which you want to perform the test
appears. Press ENTER to confirm the date:
ALL LINES:
ON DATE
TEST ON DATE: ALL LINES
DATE: XX/XX/XXXX
DATE: XX/XX/XXXX
PRESS <STEP> TO CONTINUE
ALL LINES:
ON DATE
ANNUALLY
PRESS <STEP> TO CONTINUE
TEST ANNUALLY: ALL LINES
JAN WEEK 1 MON
MONTH WEEK DAY
PRESS <STEP> TO CONTINUE