In-Tank Setup
Delivery Report Delay Time
7-26
Delivery Report Delay Time
If necessary, press STEP until you see the message:
Use this display to set a delay time between the completion of a bulk delivery and the Delivery Increase Report.
This feature prevents generation of false reports during the intervals between multi-compartment drops to one
tank. The feature also allows fuel to “settle out” after a delivery, which is especially important in manifolded tank
groups.
To enter a delay time for the selected tank, press CHANGE. Enter the delay time in minutes (up to 99). Press
ENTER to confirm your entry. The system displays:
Pump Threshold
This feature is for line manifolded tanks and is only enabled when you have the Dispense Mode set to Manifolded:
Sequential.
If necessary, press STEP until you see the message:
When the tank’s volume drops below the entered Pump Threshold percentage, pumping will switch over
immediately to the next available tank in the line manifolded set. Pumping will continue from the current tank for
another 10 seconds to avoid a disruption in dispensing during the switch over. The allowable threshold can be
from 0 to 50 percent of the tank’s full volume (see “Full Volume” on page 7-6). The default value is 10 percent.
Setting Up Additional Tanks
If you have additional tanks to set up, press STEP to return to the ENTER PRODUCT LABEL message. Then
Press TANK/SENSOR to select another tank. Repeat the setup procedures for the new tank beginning with the
section above entitled “Product Labels” on page 7-2.
If you have entered setup information for all tanks, press FUNCTION to exit.
T1: (Product Label)
DELIVERY DELAY: 01
DELIVERY DELAY: XX
PRESS <STEP> TO CONTINUE
T1: (Product Label)
PUMP THRESHOLD : 10.00