Wireless Pressurized Line Leak Detection
Labeling WPLLDs
11-2
Labeling WPLLDs
This display allows you to identify the line being monitored by a particular WPLLD (location, fuel type, etc.).
If necessary, press TANK/ SENSOR to select the desired WPLLD in the system.
When the appropriate WPLLD appears in the display, press CHANGE. (To erase a label press CHANGE again.)
Enter up to 20 alphanumeric characters for the line label and press ENTER. The system confirms your entry with
the message:
Press STEP to continue.
Piping Type
This display allows you to select the type of line being used:
• 2.0-IN. (50 mm) STEEL
• 2.0/3.0 IN. (50/76 mm) FIBERGLASS
• ENVIROFLEX PP1501
1
• ENVIROFLEX PP1500
1
• OMNIFLEX CP1501
1
• 1.5 IN. (38 mm) ENVIRON GEOFLX D
1
1
3.0 gph (11.3 lph) leak tests only on these piping types.
NOTE: to ensure correct line monitoring, you must enter the piping type that is installed for this line. The default is
Enviroflex PP1501.
Press CHANGE, enter the correct pipe type, press ENTER to confirm your choice and continue.
Piping Length
This display allows you to enter the total length of piping run between the tank and the dispensers. For manifolded
tanks, include the length of piping between the manifolded tank’s check valve and where it connects into the
product line. The allowable length in feet for each of the line types are: steel 30 to 500 ft (10 to 151 m), all others
10 to 500 (3 to 151 m)- except 3 inch (76 mm) fiberglass which is 10 to 220 (3 to 67 m).
IMPORTANT! The default length must be changed to reflect the actual line length or a Setup Data Warning will
occur.
NOTE: Refer to the Veeder-Root Line Leak Application Guide (Part No. 577013-465) for approved minimum and
maximum piping lengths.
Press STEP until you see the message:
WPLLD LINE LABEL
W1:
W1: (WPLLD Line Label)
PRESS <STEP> TO CONTINUE
W1: (WPLLD Line Label)
TYP: ENVIROFLEX PP1501
W1: (WPLLD Line Label)
LINE LENGTH: XXX