COMPATIBLE ACTUATING DEVICES
OLSEN RANGE
MAX NO. OF
DETECTORS
TYPE DESCRIPTION
Iq
uA
PER ZONE
C23BEx
* Ionisation Smoke Detector (IS Version)
100
40
C24B
Ionisation Smoke Detector
20
40
C29B
Ionisation Smoke Detector
45
40
C29BEx
Ionisation Smoke Detector (IS Version)
45
40
P24B
Photoelectric Smoke Detector
100
40
P29B
Photoelectric Smoke Detector
120
33
P76B
Photoelectric Smoke Detector
200
20
Non-Latching
P136
Duct Sampling Unit
500
8
R23B
& InfraRed Flame Detector
130
30
R24B
Dual Spectrum Infrared Flame Detector
250
5
R24BEx
Dual Spectrum Infrared Flame Detector (IS)
250
5
T56B
Heat Detector Types A, B, C, D
0
40
DLO1191A #
Beam
Detector
2800
1
* & See Notes. With the Z54 Mk2, Z56, Z500, Z72 and Z23 bases as appropriate.
TYCO RANGE
MAX. NUMBER
TYPE
DESCRIPTION
Iq uA
WITH EOL
614P
Photoelectric Smoke Detector
104
38
614I
Ionisation Smoke Detector
67
40
614CH
Carbon Monoxide & Heat Detector
80
40
614TA
Heat Detector Type A
100
40
614TB
Heat Detector Type B
100
40
614TC
Heat Detector Type C
100
40
614TD
Heat Detector Type D
100
40
MD614 Heat
Detector
60 40
MF614
Ionisation Smoke Detector
100
40
MR614
Photoelectric Smoke Detector
100
40
MR614T
High Performance Optical Smoke Detector
100
40
MU614
Carbon Monoxide Detector
50
40
T614A or
T614A Mk2
Heat Detector Type A
100
40
T614B or
T614B Mk2
Heat Detector Type B
100
40
T614C or
T614C Mk2
Heat Detector Type C
100
40
T614D or
T614D Mk2
Heat Detector Type D
100
40
S121
Infra-red Flame Detector
100
40
MS302Ex
Infra-red Flame Detector
100
40
With M614 or 5B base as appropriate.
Issue 3.04