background image

Installation Instructions

1

ESL Smoke Sensor Model 562

Preliminary

Product Summary

The ESL Smoke Sensor Model 562 (smoke alarm) is a 
Learn Mode, wireless, photoelectric smoke sensor with a 
self-contained alarm siren, a low-battery annunciator, and a 
status light. The smoke alarm is part of a security/fire 
alarm system and communicates with the system control 
panel. 

Each smoke alarm uses two 3-volt lithium batteries. The 
batteries are shipped with the unit.

Installation Guidelines

This equipment should be installed in accordance with 
the National Fire Protection Association’s Standard 72 
(National Fire Protection Association, Batterymarch 
Park, Quincy, MA 02269).

Avoid installing the unit until all construction is com-
pleted. The mounting ring may be pre-installed.

CAUTION

Not compatible with CareTaker 

Plus and custom 

versions with software versions 3.0 or earlier. 
Not compatible with Commander 2000 and custom 
versions with software versions 4.0 or earlier. 

Equipment Needed

Phillips screwdriver.

Pocket-sized slotted screwdriver.

Programming

This section describes the basic steps for adding the sensor 
to panel memory. For more detailed programming 
information, refer to the specific panel installation 
instructions.

Figure 1.Mounting Bracket.

To add the smoke alarm to panel memory:

1.

Remove smoke unit from mounting bracket.

2.

Put the panel in Program Mode/Learn Sensors.

3.

Select a sensor group and sensor number. 

4.

Remove mounting bracket.

5.

Press and hold the test button.

6.

The panel will indicate that the sensor has been 
learned. 

7.

Exit from program mode.

Note

Reinstall smoke unit on mounting bracket. 

Mounting Guidelines

Determine the best mounting location for the smoke alarm 
using the following guidelines:

NFPA 72, Chapter 2, Section 2-2.1.1.1 states as fol-
lows: “Smoke alarms shall be installed outside of each 
separate sleeping area in the immediate vicinity of the 
bedrooms and on each additional story of the family 
living unit, including basements and excluding crawl 
spaces and unfinished attics. In new construction, a 
smoke alarm also shall be installed in each sleeping 
room.”

NFPA 72, Appendix A, Section A-2.5.2.1 states as fol-
lows: “Smoke Detection - Are More Smoke Alarms 
Desirable? The required number of smoke alarms 
might not provide reliable early warning protection for 
those areas separated by a door from the areas of the 
house protected by the required smoke alarms. For this 
reason, it is recommended that the household consider 
the use of additional smoke alarms for those areas of 
increased protection. The additional areas include the 
basement, bedrooms, dining room, furnace room, util-

 

Document Number: 466-xxxx Rev. A
PRELIMINARY
April 2000

ITI Part No. 60-848-95, 60-849-95

Summary of Contents for ESL 562

Page 1: ...o add the smoke alarm to panel memory 1 Remove smoke unit from mounting bracket 2 Put the panel in Program Mode Learn Sensors 3 Select a sensor group and sensor number 4 Remove mounting bracket 5 Press and hold the test button 6 The panel will indicate that the sensor has been learned 7 Exit from program mode Note Reinstall smoke unit on mounting bracket Mounting Guidelines Determine the best moun...

Page 2: ...l install on an inside wall between 4 and 6 inches 10 and 15 cm from the ceiling see figure 5 Put smoke alarms at both ends of a bedroom hallway if the hallway is more than 30 feet 9 meters long Large rooms over 900 square feet require more than a single sensor Figure 5 Smoke alarm mounting locations Areas with rough ceilings or short transom type walls coming down from the ceiling require additio...

Page 3: ...ut the panel in sensor test mode Although not neces sary for this model it is a good practice to maintain Refer to the specific panel installation instructions for details Simon and Advent panels must be in sensor test If not you will not see anything at the panel WARNING Commander and Caretaker panels will go into alarm if not in sensor test when the test button is pressed 2 Press and hold the te...

Page 4: ...Notify fire department from a neighbor s phone WARNING If you arrive at the premises and hear sirens do not attemp to enter the building Call for emer gency assistance from a neighbor s phone Floor Plan Example Figure 9 is an example of a multilevel floor plan Use it as a guide and draw your floor plan on the next page Figure 9 Example of a floor plan Your Floor Plan When establishing your excape ...

Page 5: ...5 ESL Smoke Sensor Model 562 Emergencies Preliminary ...

Page 6: ... 848 95 Residential Installations UL 268 60 849 95 Commercial Installations This device complies with part 15 of the FCC rules Operation is subject to the following two conditions This device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation Changes or modifications not expressly approved by Interactive Te...

Reviews: