VIGILANT F08 Installation & Programming Manual
Document: LT0082
Programming
FUNCTION
PRESS KEY
INDICATED BY
1.
Enter into Zone Output
Mapping
TEST
Ancil Relay “SEL” LED Flashing
Output “ISO” LEDs Flashing
Select Output for Mapping
TEST
Selected Output “SEL” LED Flashing
Select Zones
SELECT
Selected Zone “SEL” LED ON
Output “SEL” LED Flashing
Zone Mapped to Selected
Output
TEST
“ALM” LED Steady = MAPPED
(TOGGLE)
“ALM” LED Off = NOT MAPPED
2.
Enter into Zone Latching/
Non-Latching Programming
RESET
Selected Zone “SEL” LED ON
Zone fault state non-latching indicated
by zone fault LED ON. Zone alarm
state non-latching indicated by zone
alarm LED ON.
Select Zone
SELECT
Selected Zone “SEL” LED ON
Toggle as Latching or Non-
Latching
RESET
Fault/Alarm LED ON = Non-latching,
LED OFF = Latching.
(CYCLES)
3.
Enter into Zone Input Type
Programming
SILENCE
Selected Zone “SEL” LED ON
“FLT”, “ALM”, & “ISO” LEDs ON for
Zone 1 - 8, 8 + 1, 8 + 2
Select Zone
SELECT
Selected Zone “SEL” LED ON
“FLT”, “ALM”, & “ISO” LEDs ON for:
Select Zone Delay
SILENCE
ZONE 1 = Default 2s transient
ZONE 2 = AVF/RAD
ZONE 3 = 1668 SAD
ZONE 4 = 1668 AVF/SAD
ZONE 5 = FSI 20 second
ZONE 6 = 2 secs alarm. No MCP
ZONE 7 = AVF/RAD. No MCP
ZONE 8 = Fast alarm with supervision
ZONE 8+1= Fast alarm, 15V loop pwr
ZONE 8+2=2 Secs alarm, S/C = nml
4.
Enter into Enabling or
Disabling Zones, and
Ancillary Relay Supervision
ISOLATE
Selected Zone “SEL” LED ON
Disabled Zones indicated by zone
“ISO” LED ON
ANCIL RELAY Supervision
Disabled if “ISO” LED ON
Zone auxiliary outputs are “isolatable” if
Master Alarm “ISO” LED ON.
Select Zone
SELECT
Selected Zone “SEL” LED ON
ISOLATE
“ISO” LED ON = Zone Disabled
Select Zone as Enabled or
Disabled
(TOGGLE)
“ISO” LED OFF = Zone Enabled
OR
“ISO” LED ON = SUP. Disabled
Select Ancil Relay
Supervision as Enabled or
Disabled
“ISO” LED OFF = SUP. Enabled
OR
Master Alarm “ISO” LED ON =
isolatable, OFF = output ignores zone
isolate
Select Zone Auxiliary output
isolatable or not.
Table 4.2 - Programming Key Summary - Programming Mode Enabled