5.8.3 Dry mortarless installation with installation kit TQ
Fig. 71: Dry mortarless installation into a solid wood wall or CLT wall, with installation kit TQ
1
FKR-EU
2.11
Installation kit TQ (factory assembled)
3.11
Solid wood wall / CLT wall
4.1
Solid ceiling slab / solid floor
6.13
Mineral wool strips A1,
≤
5 mm thick,
≤
1000°C,
filler as an alternative
7.10
Trim panels (fire-resistant)
7.13a
Cladding, single-layer, fire-resistant
Z
Spigot construction 370 mm
Flange construction 342 mm
*
Installation near the floor analogous to
**
Cover plate, shortened by others
#
optional
–
Up to EI 90 S
Additional requirements: dry mortarless installation
with installation kit TQ in solid wood walls
Solid wood wall or CLT wall,
≥
200 mm distance between two fire dampers in
separate installation openings
Fasten the cover plate to the solid wood or CLT wall
with 4 (for nominal widths up to 400 mm) or 12 (for
nominal widths from 450 mm) dry wall screws
Æ
≥
4.2 mm
Installation
Solid wood walls > Dry mortarless installation with installation ...
Fire damper FKR-EU
95