Lightweight partition wall, half-timbered construction with cladding on both sides
Fig. 52: Lightweight partition wall, half-timbered construction with cladding on both sides
5.1
Dry wall screw
6.8
Infill*
7.9
Timber structure
7.11
Trim panels, double layer, staggered joints
7.13
Cladding
*
Cavities completely filled with mineral wool
≥
50 kg/m³, bricks, aerated concrete, lightweight
concrete, reinforced concrete or clay
☐
A
Clear installation opening
☐
A1
Opening in the half-timbered construction,
☐
A1 =
☐
A + (4
×
trim panels)
Additional requirements: lightweight partition walls with timber support structure / half-timbered construc-
tion
Timber stud wall or half-timbered construction,
Installation opening
☐
A [mm]
Installation type
Nominal size
Æ
nominal width
315
355
400
450
500
560
630
710
800
Mortar-based installation
☐
A =
Æ
nominal width + max. 450 mm
☐
A1 =
☐
A + (4
×
trim panels)
Dry mortarless installation with installa-
tion kit TQ
1, 2
435
475
520
570
620
680
750
830
920
Dry mortarless installation with fire batt
☐
A =
Æ
nominal width + 80 – 1200 mm
1)
Installation opening tolerance
±
2 mm
2)
Installation kit TQ is available only for FKR-EU with spigot