5.8.2 Mortar-based installation
Fig. 69: Mortar-based installation into a solid wood wall or CLT wall
1
FKR-EU
2.1
Mortar
3.11
Solid wood wall / CLT wall
4.1
Solid ceiling slab / solid floor
5.13
Wood screw or pin
7.10
Trim panels
7.13a
Cladding, single-layer, fire-resistant
7.14
Reinforcing board of the same material
(required for W < 100 mm, optionally on the
operating or installation side)
Z
Spigot construction 370 mm
Flange construction 342 mm
*
Installation near the floor analogous to
#
optional
–
Up to EI 90 S
Installation
Solid wood walls > Mortar-based installation
Fire damper FKR-EU
93
Summary of Contents for FKR-EU
Page 162: ...Fire damper FKR EU 162 ...
Page 163: ...Fire damper FKR EU 163 ...
Page 164: ...Fire damper FKR EU 164 ...