5.5 Solid walls
5.5.1 General
Fig. 20: Solid walls – arrangement / distances, side by side arrangement also applies to arrangement under one
another
1
FKR-EU
3.1
Solid wall
s1
Perimeter gap
s2
Distance between the fire dampers
Spigot construction 40 – 225 mm
Flange construction 80 – 225 mm
Installation type
Installation opening [mm]
Distance [mm]
s1
s2
Mortar-based installation
Æ
nominal width + max. 450
mm
≤
225
40 – 225
2
Dry mortarless installation with fire batt
1
Æ
nominal width + max. 1200
mm
40 – 600
40 – 600
2
1)
Observe maximum permitted size of the fire batt!
2)
Flange construction 80 – 225 mm or 80 – 600 mm
Additional requirements: solid walls
Solid wall
Distances and installation orientations,
Installation
Solid walls > General
Fire damper FKR-EU
38