Fig. 41: Mortar-based installation – multiple occupancy of an installation opening
1
FKR-EU
2.1
Mortar
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
3.6
Compartment wall or safety wall with metal sup-
port structure, cladding on both sides
6.5
Mineral wool (depending on wall construction)
7.10
Trim panels
Z
Spigot construction 370 mm
Flange construction 342 mm
s2
Spigot construction 40 – 225 mm
Flange construction 80 – 225 mm
#
Depending on the wall structure
Up to EI 90 S
Installation
Lightweight partition walls > Mortar-based installation – multiple occupancy...
Fire damper FKR-EU
60
Summary of Contents for FKR-EU
Page 162: ...Fire damper FKR EU 162 ...
Page 163: ...Fire damper FKR EU 163 ...
Page 164: ...Fire damper FKR EU 164 ...