Minimum number of fixing points in the bare ceiling
B
A
≥
315
≥
500
≥
800
≥
1100
≥
1400
≥
1700
≥
2000
≥
315
4
6
8
10
12
14
16
≥
500
6
8
10
12
14
16
18
≥
800
8
10
12
14
16
18
20
≥
1100
10
12
14
16
18
20
22
≥
1400
12
14
16
18
20
22
24
≥
1700
14
16
18
20
22
24
26
≥
2000
16
18
20
22
24
26
28
Additional requirements: mortar-based installation
into solid ceiling slab with concrete base – multiple
occupancy of an installation opening
Total fire damper area (
Æ
nominal width)
≤
4.8 m
2
The number of fire dampers in an installation
opening is limited by their damper size
(
Æ
nominal width) and the overall area of the fire dampers (4.8 m
2
).
The dampers can be arranged in one or two rows.
Structural properties of the ceiling construction,
including the attachment to the mortar/concrete or
any required reinforcement, have to be evaluated
and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation into the concrete ba...
Fire damper FKR-EU
119