3.6
Compartment wall or safety wall with metal sup-
port structure, cladding on both sides
6.2
Mineral wool,
≥
1000 °C,
≥
80 kg/m³
6.5
Mineral wool (depending on wall construction)
6.11
Insulating strip (depending on wall construction)
7.1
UW section
7.3
UA section
7.5
Steel support structure
7.10
Trim panels *
7.11
Trim panels, fire-resistant, 2-ply, max. 25 mm
(alternative to 6.2 and 7.14)
7.23
Sheet steel insert depending on wall manufac-
turer
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
*
The total thickness of the trim panels must not
exceed 25 mm
#
optional
–
Up to EI 90 S
Up to EI 60S
–
EI 30 S
Dry mortarless installation into a lightweight partition wall, below a flexible ceiling joint with installation kit
TQ
Fig. 44: Dry mortarless installation into a lightweight partition wall, below a flexible ceiling joint with installation kit TQ
1
FKR-EU
2.11
Installation kit TQ (factory assembled)
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
3.6
Compartment wall or safety wall with metal sup-
port structure, cladding on both sides
4.1
Solid ceiling slab
5.1
Dry wall screw
6.5
Mineral wool (depending on wall construction)
6.13
Mineral wool strips A1,
≤
5 mm thick,
≤
1000°C,
filler as an alternative
7.1
UW section
7.10
Trim panels
7.13
Cladding
7.21
Ceiling joint strips (e.g. 4
× ≥
10 mm)
Z
Spigot construction 370 mm
Flange construction 342 mm
#
Depending on the wall structure
Up to EI 90 S
Note:
representative illustration. The distance to the ceiling depends on the design of the flexible ceiling joint, the
expected ceiling subsidence and the specifications of the wall manufacturer.
Additional requirements: dry mortarless installation
with installation kit TQ in lightweight partition walls
Lightweight partition wall or compartment wall,
≥
200 mm distance between two fire dampers in
separate installation openings
Fasten the cover plate with 4 (for nominal widths up
to 400 mm) or 12 (for nominal widths from 450 mm)
dry wall screws
Æ
≥
4.2 mm to the metal support
structure
Installation
Lightweight partition walls > Dry mortarless installation with installation ...
Fire damper FKR-EU
64
Summary of Contents for FKR-EU
Page 162: ...Fire damper FKR EU 162 ...
Page 163: ...Fire damper FKR EU 163 ...