5.11.12 Mortar-based installation in conjunction with lightweight ceilings
Fig. 97: Mortar-based installation into solid ceiling slab in conjunction with lightweight ceiling (Cadolto system),
shown upright (also applicable for suspended arrangement)
1
FKR-EU
2.1
Mortar
2.2
Reinforced concrete
4.3
Modular ceiling (Cadolto system), installation
according to manufacturer's instructions and gen-
eral appraisal certificate
7.5
Steel support structure
7.17
Trimmers, steel support structure
7.19
Fire-resistant cladding
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
Up to EI 120 S
Additional requirements: mortar-based installation
into solid ceiling slabs in conjunction with light-
weight ceilings
Modular ceiling, (Cadolto system),
≥
40 mm distance from fire damper to load-bearing
structural elements
Distance of
≥
40 mm between two fire dampers
(80 mm for flange construction). When you install
two fire dampers next to each other into the same
opening, the concrete bed between the two fire
dampers must not exceed 225 mm.
1.
Create the installation opening so that a sur-
rounding concrete cover of at least 50 mm is
ensured.
2.
Create a partial concrete ceiling around the fire
damper,
≥
150 mm,
≥
150 mm thick.
Note:
Structural and fire resistance properties of the ceiling
construction, including the attachment to the con-
crete or any required reinforcement, have to be eval-
uated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation in conjunction with ...
Fire damper FKR-EU
126