5.6.5 Dry mortarless installation without installation kit
Fig. 45: Dry mortarless installation into a lightweight partition wall, without installation kit
1
FKR-EU
2.19
Joint filler (ready-to-use putty or equivalent)
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
6.5
Mineral wool (depending on wall construction)
7.13
Cladding
–
Up to EI 60 S
B
Operating side
Additional requirements: dry mortarless installation
into lightweight partition walls without installation
kit
Lightweight partition wall,
≥
200 mm distance between two fire dampers
≥
75 mm distance from fire damper to load-bearing
structural elements
1.
Create a circular installation opening with nominal
width +20 mm.
2.
Chamfer the outer layer of the cladding all round
on both sides and completely close off the sur-
rounding gap on both sides with joint filler to the
depth of the cladding.
Installation
Lightweight partition walls > Dry mortarless installation without installati...
Fire damper FKR-EU