Mortar-based installation into a solid ceiling slab, FKR-EU and FK2-EU combined
Fig. 84: Mortar-based installation in solid ceiling slab, combined, FKR-EU and FK2-EU, shown upright (also appli-
cable for suspended arrangement)
1b
FKR-EU
1a
FK2-EU up to B
×
H
≤
800 × 400 mm
2.1
Mortar
2.2
Concrete
4.1
Solid ceiling slab
Z
Spigot construction 370 mm
Flange construction 342 mm
s2
Spigot construction 40 – 225 mm
Flange construction 80 – 225 mm
Up to EI 90 S
Note on combined installation:
Total fire damper surface area
≤
1.2 m².
The number of fire dampers in an installation opening is limited by their size (B
×
H for FK2-EU and /or
Æ
nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²).
Alternative installation orientations of side-by-side possible. Details are available upon request.
For installation details FK2-EU, see the installation and operating manual for this fire damper type.
Structural properties of the ceiling construction, including the attachment to the mortar/concrete or any required
reinforcement, have to be evaluated and ensured by others.
Distance of FKR-EU to a FK-EU 75 – 225 mm (flange construction 80 – 225 mm)
Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s...
Fire damper FKR-EU
110