Dry mortarless installation with installation kit TQ in wooden beam / laminated beam ceiling, suspended
Fig. 103: Dry mortarless installation with installation kit TQ into wooden beam / laminated beam ceiling, suspended
(illustration representative, alternative ceiling construction possible on request)
1
FKR-EU
2.11
Installation kit TQ (factory assembled)
5.1
Dry wall screw
6.5
Mineral wool filling depending on ceiling con-
struction
7.11
Trim panel, same construction as 7.19
7.15
Wood sheet, min. 600 kg/m³
7.16
Wooden beam / gluelam min. 100
×
80 mm
(reduce distances between wooden beams to the
size of the installation opening)
7.17
Trimmers, wooden beam / glued laminated
timber min. 100
×
80 mm
7.19
Fire-resistant cladding (ceiling-dependent)
Z
Spigot construction 370 mm
Flange construction 342 mm
Up to EI 90 S
Up to EI 60 S
EI 30 S
Additional requirements: dry mortarless installation
with installation kit TQ into wooden beam / lami-
nated beam ceilings
≥
75 mm distance from the fire damper to load-
bearing structural elements (structure 100 mm)
≥
200 mm distance between two fire dampers in
separate installation openings
Fasten the cover plate to the wooden beam / glue-
laminated beam ceiling with 4 (for nominal widths up
to 400 mm) or 12 (for nominal widths from 450 mm)
dry wall screws
Æ
≥
4.2 mm
Note:
Structural and fire resistance properties of the ceiling
construction, including the attachment to the con-
crete or any required reinforcement, have to be eval-
uated and ensured by others.
Installation
Wooden beam ceilings > Dry mortarless installation with installation ...
Fire damper FKR-EU
132