Installation situations
Supporting con-
struction
Installation location
Minimum
thickness
[mm]
Class of per-
formance EI TT
(v
e
–h
o
, i ↔ o) S
up to
Installation
type
Chapter
in, fire batt
110
EI 60 S
W
105
EI 30 S
W
Half-timbered con-
structions
in
140
EI 90 S
N
110
EI 30 S
N
in, combined assembly
140
EI 90 S
N
in, multiple mounting
140
EI 90 S
N
in, installation kit TQ
140
EI 90 S
E
110
EI 30 S
E
in, fire batt
140
EI 60 S
W
110
EI 30 S
W
Solid wood / cross
laminated timber
walls
in
95
EI 90 S
N
in, installation kit TQ
95
EI 90 S
E
in, fire batt
95
EI 60 S
W
Shaft wall with
metal support
structure
in
90
EI 90 S
N
90
3
EI 30 S
N
80
EI 90 S
N
75
EI 30 S
N
in, combined assembly
90
EI 90 S
N
Shaft wall without
metal support
structure
in
50
EI 90 S
N
Solid ceiling slabs
in
100 (150)
3
EI 120 S
N
100 (150)
3
EI 90 S
N
in, combined assembly
150
EI 90 S
N
in, multiple mounting
150
EI 90 S
N
in, with concrete base
100
EI 90 S
N
in, with concrete base
100
EI 120 S
N
in, with concrete base, com-
bined assembly
100
EI 90 S
N
in, with concrete base, multiple
mounting
100
EI 90 S
N
in, hollow stone ceilings
150
EI 90 S
N
in, hollow chamber ceilings
150
EI 90 S
N
1)
Gypsum wall boards EN12859
2)
The class of performance depends on the installation details
3)
Thickness increased near the installation opening
4)
Cadolto system
5)
Depending on local conditions
N = Mortar-based installation
E = Installation kit
W = Fire batt
E = Dry mortarless installation
Installation
Installation situations
Fire damper FKR-EU
25