5.6.4 Dry mortarless installation with installation kit TQ
Dry mortarless installation into a lightweight partition wall, with installation kit TQ
Fig. 42: Dry mortarless installation into a lightweight partition wall, with installation kit TQ
1
FKR-EU
2.11
Installation kit TQ (factory assembled)
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
3.6
Compartment wall or safety wall with metal sup-
port structure, cladding on both sides
4.1
Solid ceiling slab
6.2
Mineral wool,
≥
1000 °C,
≥
80 kg/m³
6.5
Mineral wool (depending on wall construction)
6.13
Mineral wool strips A1,
≤
5 mm thick,
≤
1000°C,
filler as an alternative
7.10
Trim panels
7.11
Trim panels, fire-resistant, 2-ply, max. 25 mm
(alternative to 6.2 and 7.14)
7.13
Cladding
7.14
Reinforcing board, made of wall panels (up to
the fire damper casing)
9.2
Extension piece or duct
*
Cover plate, shortened by others
–
Up to EI 90 S
Note:
– valid for all wall constructions and wall thicknesses.
and valid for all wall thicknesses with a single stud frame.
Installation