5.11.9
Mortar-based installation into composite ceilings
Fig. 94: Mortar-based installation into composite ceilings, shown upright (also applicable for suspended arrange-
ment)
1
FKR-EU
2.1
Mortar
2.2
Concrete
4.10
Composite ceiling* (concrete)
7.8
Steel girder
7.27
Profile sheet metal
Z
Spigot construction 370 mm
Flange construction 342 mm
Up to EI 90 S
*
Illustration representative, other ceiling construc-
tions possible according to local conditions and
ceiling manufacturers
Additional requirements: mortar-based installation
into composite ceilings
Composite ceiling,
≥
40 mm distance from fire damper to load-bearing
structural elements
≥
200 mm distance between two fire dampers in
separate installation openings
Note:
Structural and fire resistance properties of the ceiling
construction, including the attachment to the con-
crete or any required reinforcement, have to be eval-
uated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation into composite ceili...
Fire damper FKR-EU
123