ECM Overview and Setup
90
UNT-SVX07E-EN
Configuration Examples
Example 1.
To view the value of parameters without
saving. In this case we wish to verify that the “Low Speed
Value” for Motor 1 is set correctly to 800 rpm.
We start with the motor control board scrolling status
display and proceed as follows:
Example 2.
We wish to change the change the value of
Low Speed to 820 rpm:
We will continue from the previous example as shown
below, using a long press to “save” the new desired value.
Note:
If the display has timed out and returned to the
status loop, repeat Example 1 to arrive back at this
example’s starting point.
Table 39. Button actuation levels
Button
Menu/Set
Duration
Action
Short Press in
Status Display
<1 sec
None
Short Press in Configuration Display
Toggles between parameter name and value without saving
(abandons value if changed).
Long Press/Hold
in Status Display
>3 sec
Enters the configuration menu
Long Press/Hold
in Configuration Display
>3 sec
If on a parameter name, toggles to the value. If on a parameter value,
saves the value settings and returns to the parameter name as
confirmation.
Button
Decrement
Duration
Action
Short Press in
Status Display
<1 sec
None
Short Press in Configuration Display
<1 sec
Scrolls through parameter names, or decreases value of parameter.
Long Press/Hold
in Status Display
>3 sec
n/a
Long Press/Hold
in Configuration Display
>3 sec
Faster scroll through parameter name, or faster decrease of values of
parameters.
Button
Increment
Duration
Action
Short Press in
Status Display
<1 sec
None
Short Press in Configuration Display
<1 sec
Scrolls through parameter names, or increases value of parameter.
Long Press/Hold
in Status Display
>3 sec
n/a
Long Press/Hold
in Configuration Display
Faster scroll through parameter name, or faster increase of values of
parameters.
Figure 80. Verify low speed value
Figure 81. Change value of low speed