Installation - Zone Sensors
UNT-SVX07E-EN
67
Associating Sensor to Receiver
To associate the sensor to the receiver:
1.
Remove the sensor cover by firmly pressing the thumb
tab at the bottom of the cover and pulling the cover
away from the back plate.
2. Verify that the sensor is set to the same address as the
receiver it is to be associated with.
3. Power the sensor by removing the insulation strip from
between the two batteries. See
Figure 56
.
Association is automatically initiated between the sensor
and the receiver. When LED3 on the receiver stops
blinking, association has been established.
If the first association attempt is unsuccessful, the sensor
automatically re-attempts association with the receiver
every 10 minutes.
Note:
An associated sensor that has lost communication
with the receiver will transmit an association
request every 50 minutes. You can manually
initiate association (see
“Manual Association,”
page 134
”).
Testing Signal Strength and Battery
To verify that the association process was successful and
that the batteries have adequate charge:
1.
Firmly press and release the Test button on the bottom
of the sensor as illustrated in
Figure 57
.
2. For model WZS, view LED1, LED2, and LED3 to
determine the signal strength. View LED5 to determine
the battery status (see
Figure 57
for model WZS
sensors).
Note:
The LEDs will turn Off after 5 seconds to
conserve battery strength.
For model WDS, determine the signal strength and
battery status by viewing the symbols on the sensor
display (see
Figure 58
for model WDS sensors).
3. Record the results in your commissioning statement.
Figure 56.
Power sensor by removing insulation strip
Figure 57.
Wireless Zone Sensor (WZS) with LED lights
to test for battery strength
Figure 58.
Wireless Display Sensor (WDS) showing
battery strength
LED1
LED2
LED3
LED5
Test button
Push firmly,
then release
Test button
Push firmly,
then release