Dimensions and Weights
16
UNT-SVX07E-EN
Component Data
Table 1.
Fan coil and cabinet heater component data
Unit Size
02
03
04
06
08
10
12
Coil Data
Face Area (ft
2
)
0.80
0.80
1.10
1.60
2.10
3.20
3.20
L x D x H (in.)
2-Row
15 x 1.7 x 8
15 x 1.7 x 8
20 x 1.7 x 8
29.5 x 1.7 x 8
38 x 1.7 x 8
57 x 1.7 x 8
57 x 1.7 x 8
3-Row
15 x 2.6 x 8
15 x 2.6 x 8
20 x 2.6 x 8
29.5 x 2.6 x 8
38 x 2.6 x 8
57 x 2.6 x 8
57 x 2.6 x 8
4-Row
15 x 3.5 x 8
15 x 3.5 x 8
20 x 3.5 x 8
29.5 x 3.5 x 8
38 x 3.5 x 8
57 x 3.5 x 8
57 x 3.5 x 8
Volume (gal.)
1-Row (Heat)
0.06
0.06
0.08
0.11
0.14
0.21
0.21
2-Row
0.12
0.12
0.15
0.22
0.28
0.42
0.42
3-Row
0.18
0.18
0.23
0.33
0.42
0.62
0.62
4-Row
0.24
0.24
0.30
0.44
0.56
0.83
0.83
Fins per inch
2-Row
12
12
12
12
12
12
12
3-Row
12
12
12
12
12
12
12
4-Row
12
12
12
12
12
12
12
Reheat Coil Data (1-Row), Standard or High-Capacity
1
Hot Water or Steam
Face Area (ft
2
)
0.60
0.60
0.80
1.20
1.60
2.40
2.40
L x D x H (in.)
15 x 1.5 x 6
15 x 1.5 x 6
20 x 1.5 x 6
29.5 x 1.5 x 6
38 x 1.5 x 6
57 x 1.5 x 6
57 x 1.5 x 6
Volume (gal.)
0.12
0.12
0.15
0.22
0.28
0.42
0.42
Standard Capacity
1
Fins/in.
4
4
4
4
4
4
4
High-Capacity
1
Fins/in.
12
12
12
12
12
12
12
Fan/Motor Data
Fan Quantity
1
1
1
2
2
3
3
Size — Dia x Width (in.)
6.31 x 4
6.31 x 6.5
6.31 x 7.5
6.31 x 6.5
6.31 x 7.5
(1) 6.31 x 7.5
6.31 x 7.5
Size — Dia x Width (in.)
(2) 6.31 x 6.5
Motor Quantity
1
1
1
1
1
2
2
Filter Data
1-in. Throwaway and Pleated Media
Quantity
1
1
1
1
1
1
1
Size (in.)
8-7/8 x 19-1/8 8-7/8 x 19-1/8 8-7/8 x 24-1/8 8-7/8 x 33-5/8 8-7/8 x 42-1/8 8-7/8 x 61-1/8 8-7/8 x 61-1/8
1-in. Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity
1
1
1
1
1
1
1
Size (in.)
5-1/2 x 19-1/8 5-1/2 x 19-1/8 5-1/2 x 24-1/8 5-1/2 x 33-5/8 5-/2 x 42-1/8 5-1/2 x 61-1/8 5-1/2 x 61-1/8
Note:
1
Standard and high-capacity reheat coils share the same component data except that standard capacity reheat coils have 4 fins/in. while high-capacity
reheat coils have 12 fins/in.
Table 2.
Low vertical fan coil component data
Unit Size
03
04
06
Coil Data
Face Area (ft
2
)
1.10
1.60
2.10
L x D x H (in.)
2-Row
20 x 1.7 x 8
29.5 x 1.7 x 8
38 x 1.7 x 8
3-Row
20 x 2.6 x 8
29.5 x 2.6 x 8
38 x 2.6 x 8
Volume (gal.)
1-Row (Heat)
0.08
0.11
0.14
2-Row
0.15
0.22
0.28
3-Row
0.23
0.33
0.42
Fins per inch
2-Row
12
12
12
3-Row
12
12
12
Fan/Motor Data
Fan Quantity
1
1
1
Size — Dia x Width (in.)
5.00 x 23.00
5.00 x 32.00
5.00x 41.00
Motor Quantity
1
1
1
Filter Data
1-in. Throwaway
Quantity
1
1
1
Size — in.
8-7/8 x 24-1/8
8-7/8 x 33-5/8
8-7/8 x 42-1/8
Note:
Low vertical model not available for Force Flo cabinet heaters.