Startup
108
UNT-SVX07E-EN
modulating outputs open further and binary outputs are
energized longer. At 100 percent capacity, the heating
valve is fully open (3-wire modulating valves) or on
continuously (two-position valves).
The fan output(s) normally run continuously during the
occupied and occupied standby modes, but cycle between
high and off speeds with heating/cooling during the
unoccupied mode. When in the occupied mode or
occupied standby mode and the fan speed is set at the
high, medium, or low position, the fan runs continuously
at the selected speed. Refer to the Troubleshooting section
for more information on abnormal fan operation.
When the unit’s supply fan is set to auto, the controller’s
configuration determines the fan speed when in the
occupied mode or occupied standby mode. The fan runs
continuously at the configured heating fan speed or
cooling fan speed. For all fan speed selections except off,
the fan cycles off during unoccupied mode.
The economizer outdoor air damper is never used as a
source of heating. Instead, the economizer damper (when
present) is only used for ventilation; therefore, the damper
is at the occupied minimum position in the occupied
mode. The damper control is primarily associated with
occupied fan operation.
Fan Mode Operation
For multiple fan speed applications, the controller offers
additional fan configuration flexibility. Separate default
fan speeds for heating and cooling modes can be
configured. The fan runs continuously for requested
speeds (off, high, medium, or low). When the fan mode
switch is in the Auto position or a hard-wired fan mode
input does not exist, the fan operates at the default
configured speed. See
Table 49
for default fan
configuration for heat and cool mode. During unoccupied
mode, the fan cycles between high speed and off with
heating and cooling fan modes. If the requested speed is
off, the fan always remains off.
During dehumidification, when the fan is on Auto, the fan
speed can switch depending on the error. Fan speed
increases as the space temperature rises above the active
cooling setpoint.
Additional flexibility built into the controller allows you to
enable or disable the local fan switch input. The fan mode
request can be either hard-wired or communicated to the
controller. When both are present, the communicated
request has priority over the hard-wired input. See
Table 50
,
Table 51
, and
Table 52
.
Continuous Fan Operation
During occupied and occupied standby modes, the fan
normally is on. For multiple speed fan applications, the fan
normally operates at the selected or default speed (off,
high, medium, or low). When fan mode is auto, the fan
operates at the default fan speed.
During unoccupied mode, the controller controls the fan
off. While unoccupied, the controller heats and cools to
maintain the unoccupied heating and cooling setpoints. In
unoccupied mode, the fan is controlled on high speed only
with heating or cooling.
The unit fan is always off during occupied, occupied
standby, and unoccupied modes when the unit is off due
to a diagnostic or when the unit is in the off mode due to
the local zone sensor module, a communicated request, or
the default fan speed (off).
If both a zone sensor module and communicated request
exist, the communicated request has priority.
Table 49. Fan configuration for Tracer ZN520 units
Auto Fan Operation
Fan Speed Default
Heating
Continuous
Off
Low
Medium
High
Cooling
Continuous
Off
Low
Medium
High
Table 50. Local fan switch enabled
Communicated Fan Speed
Input
Fan Switch
(Local)
Fan
Operation
Off
Ignored
Off
Low
Ignored
Low
Medium
Ignored
Medium
High
Ignored
High
Auto
Off
Low
Medium
High
Auto
Off
Low
Medium
High
Note:
Auto (configured default, determined by heat/cool mode)
Table 51.
Fan operation in heating and cooling modes
Fan
Mode
Heating
Cooling
Occupied Unoccupied Occupied Unoccupied
Off
Off
Off
Off
Off
Low
Low
Off/high
Low
Off/high
Medium
Med
Off/high
Med
Off/high
High
High
Off/high
High
Off/high
Auto
Default fan
speed
Off/high
Default fan
speed
Off/high
Table 52. Local fan switch disabled or not present
Communicated Fan
Speed Input
Fan Operation
Off
Off
Low
Low
Medium
Medium
High
High
Auto (or not present)
Auto (fan runs at the default
speed)