Wireless Sensor Specifications
Agency Compliance
Table 23. Wireless sensor specifications
Component
Type
Sensor operating temperature
32°F to 122°F
Receiver operating temperature
-40°F to 158°F
Storage temperature
-40°F to 185°F
Storage and operating humidity range
5% to 95%, non-condensing
Accuracy
0.5°F over a range of 55ºF to 85°F
Resolution
0.125°F over a range of 60°F to 80°F 0.25°F when outside this range
Setpoint functional range (WDS only)
50°F to 89.6°F
Receiver voltage
24 V nominal ac/dc ±10%
Receiver power consumption
<1 VA
Housing
Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating, suitable for application in a
plenum
Mounting
3.24 in (8.26 cm) for 2 mounting screws (supplied)
Sensor battery
(2) AA, 1.5 V, 2800 mAh, lithium, 5-year life, UL listed
Range
(a)
Open range: 2,500 ft (762 m) (packet error rate = 2 percent)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
Output power
100 mW
Radio frequency
2.4 GHz (IEEE Std 802.15.4-2003 compliant)
(2405 to 2480 MHz, 5 MHz spacing)
Radio channels
16
Address range
000 to 999
Minimum time between transmissions
30 seconds
Maximum time between transmissions
15 minutes
(a) Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and must be determined during site eval-
uation.
Table 24. Agency compliance information for wireless sensors
Agency
Compliance
United States compliance
(all models)
UL listed: UL 94-5VA Flammability rating
UL 916: Energy management equipment
FCC CFR47, Section 15.247 & Subpart E Digital Modulation Transmission with no SAR (FCC Identification TFP-
13651127)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications not expressly approved by the party responsible for compliance could void
the user’s authority to operate the equipment.
20 cm separation distance:
To comply with FCC’s RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for
this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must
not be co-located or operating in conjunction with any other antenna or transmitter.
Canada compliance
(all models)
CSA22.2 No. 205-M1983 Signal Equipment
Industry Canada (Certification no: IC: 6178A-13651127)
Industry Canada statement:
the term “IC” before the certification/registration number signifies only that the Industry Canada technical
specifications were met.
Section 14 of RSS-210:
The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not
emit RF field in excess of Health Canada limits for the general population.
IEEE compliance for radio
frequency range
(all models)
IEEE 802.15.4-2003, IEEE Standard for Information Technology—Telecommunications and information
exchange between systems—Local and metropolitan area networks—Specific requirements, Part 15.4: Wireless
Medium Access Control (MAC) and Physical Layer (PHY) Specifications for Low Rate Wireless Personal Area
Networks (LR-WPANs)