6.5.1.7 Inverse time overcurrent elements OCI, EFI
The testing circuit is shown in Figure 6.5.11.
Single-phase
current
source
A
TB 1
- 2
-1
- 7
- 8
I a
IN
GRT100
Monitoring
jack
A
0V
TB 4 - A16
- A17
E
DC
power
supply
Time
counter
Start
Stop
OV
Figure 6.5.11 Testing OCI and EFI (Model 100s, 200s)
One of the four inverse time characteristics can be set, and the output signal numbers are as
follows:
Element
Signal number
1OCI, 2OCI, 3OCI
50, 56, 62
1EFI, 2EFI, 3EFI
73, 76, 79
Fix the time characteristic to test by setting the OCI or EFI on the "OC" screen.
"Setting (change)" sub-menu
"Protection" screen
"Trip" screen
"Protection element"
screen
"OC" screen
The testing procedure is as follows:
Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen.
Enter a signal number to observe the OCI or EFI output at monitoring jack A and press the
ENTER
key.
Apply a test current and measure the operating time. The magnitude of the test current should
be between 1.2
I
s
to 20
I
s
, where I
s
= (CT secondary rated current) × (OCI or EFI current
setting).
Calculate the theoretical operating time using the characteristic equations shown in Section
2.11.4. Check that the measured operating time is within the error mentioned below.
Accuracy: Standard, Very and Long-time inverse: IEC 60255-3 class 5
Extremely inverse: IEC 60255-3 class 7.5
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......