56
6
F
2
S
0
7
8
9
Table 3.2.2 Binary Input Signals
Signal Names
Driving Contact Condition / Function Enabled
BISW
Mechanical trip
Closed when external device operated. / Initiate trip command
from operation of external device.
1
Mechanical trip
Closed when external device operated. / Initiate trip command
from operation of external device.
2
Mechanical trip
Closed when external device operated. / Initiate trip command
from operation of external device.
3
Mechanical trip
Closed when external device operated. / Initiate trip command
from operation of external device.
4
Indication reset
Closed to reset TRIP LED indication. / Reset indication
externally.
5
Signal for event record Closed when external device operated. / Initiate event record
with external signal.
14
Signal for event record Closed when external device operated. / Initiate event record
with external signal.
15
Signal for event record Closed when external device operated. / Initiate event record
with external signal.
16
GRT100
Mechanical trip
Mechanical trip
Mechanical trip
BI1
BI2
BI3
(
)
(+)
0V
1
(Inv)
BISW1 (Norm)
1
PLC function
Programmable
logic
BI1
Protection
schemes
Signal No.
BI2
(Inv)
BISW2 (Norm)
1
(Inv)
BISW3 (Norm)
1
BI3
Figure 3.2.1 Logic Level Inversion
3.2.2
Binary Output Signals
The number of output binary signals and their output terminals vary depending on the relay
models. See Appendix G for details. For all models, all outputs except the tripping command,
signal for command protections and relay failure signal can be configured.
The signals shown in the signal list in Appendix B can be assigned to the output relay
individually or in arbitrary combinations. Signals can be combined using either an AND circuit
or OR circuit with 6 gates each as shown in Figure 3.2.2. The output circuit can be configured
according to the setting menu. Appendix D shows the factory default settings.
A 0.2s delayed drop-off timer can be attached to these assigned signals. The delayed drop-off
time is disabled by the scheme switch [BOTD].
The relay failure contact closes when a relay defect or abnormality in the DC power supply
circuit is detected.
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......