Setting
The following shows the setting elements for the overcurrent protection and their setting ranges.
Element
Range
Step
Default
Remarks
1OC
0.10
20.0(*)
0.01
2.00
Definite time overcurrent (line)
2OC
0.10
20.0(*)
0.01
2.00
Definite time overcurrent (line)
3OC
0.10
20.0(*)
0.01
2.00
Definite time overcurrent (line)
T1OC
0.00
10.00s
0.01s
1.00s
Delayed tripping for 1OC
T2OC
0.00
10.00s
0.01s
1.00s
Delayed tripping for 2OC
T3OC
0.00
10.00s
0.01s
1.00s
Delayed tripping for 3OC
1OCI
0.10
5.00(*)
0.01
1.00
Inverse time overcurrent (line)
2OCI
0.10
5.00(*)
0.01
1.00
Inverse time overcurrent (line)
3OCI
0.10
5.00(*)
0.01
1.00
Inverse time overcurrent (line)
T1OCI
0.05
1.00
0.01
1.00
Time multiplier setting for 1OCI
T2OCI
0.05
1.00
0.01
1.00
Time multiplier setting for 2OCI
T3OCI
0.05
1.00
0.01
1.00
Time multiplier setting for 3OCI
1EF
0.10
20.00(*)
0.01
2.00
Definite time overcurrent (neutral)
2EF
0.10
20.00(*)
0.01
2.00
Definite time overcurrent (neutral)
3EF
0.10
20.00(*)
0.01
2.00
Definite time overcurrent (neutral)
T1EF
0.00
10.00s
0.01s
1.00s
Delayed tripping for 1EF
T2EF
0.00
10.00s
0.01s
1.00s
Delayed tripping for 2EF
T3EF
0.00
10.00s
0.01s
1.00s
Delayed tripping for 3EF
1EFI
0.10
5.00(*)
0.01
1.00
Inverse time overcurrent (neutral)
2EFI
0.10
5.00(*)
0.01
1.00
Inverse time overcurrent (neutral)
3EFI
0.10
5.00(*)
0.01
1.00
Inverse time overcurrent (neutral)
T1EFI
0.05
1.00
0.01
1.00
Time multiplier setting for 1EFI
T2EFI
0.05
1.00
0.01
1.00
Time multiplier setting for 2EFI
T3EFI
0.05
1.00
0.01
1.00
Time multiplier setting for 3EFI
Scheme switch
M1OCI to M3OCI
M1EFI to M3EFI
Long-Std-Very-Ext
Long-Std-Very-Ext
Std
Std
Inverse time characteristic selection of
OCI elements
EFI elements
Scheme switch
[1OC1] to [3OC5]
[1OCI1] to [3OCI5]
[1EF1] to [3EF5]
[1EFI1] to [3EFI5]
Off/On
(**)
Enable or disable tripping by
OC elements
OCI elements
EF elements
EFI elements
(*) : Multiplier of CT secondary rated current
(**) : Default settings are dependent on the models. See Appendix H.
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......