4.2.4.4 Displaying the Status of the Time Synchronization Source
The internal clock of the GRT100 can be synchronized with external clocks such as the
IRIG-B time standard signal clock, RSM (relay setting and monitoring system) clock,
IEC60870-5-103 or Modbus. To display on the LCD whether these clocks are active or
inactive and which clock the relay is synchronized with, do the following:
Select 2 (= Status) on the top "MENU" screen to display the "Status" screen.
Select 4 (= Time sync source) to display the status of time synchronization sources.
I E C :
a c t i v e
I n
3
/
1
/ 2 T i m e s y n c
* I R I G :
A c t i v
h r o n i z a t o n
i
s o u r c e
e
R S M :
a c t i v e
I n
M O D :
a c t i v e
I n
The asterisk on the far left shows that the internal clock is synchronized with the marked source
clock. If the marked source clock is inactive, the internal clock runs locally.
For details of the setting time synchronization, see Section 4.2.6.6.
4.2.4.5 Adjusting the Time
To adjust the clock when the internal clock is running locally, do the following:
Select 2 (= Status) on the top "MENU" screen to display the "Status" screen.
Select 5 (= Clock adjustment) to display the setting screen.
/ 2
1 2 / F e b / 1 9 9 8
2 2 : 5 6 : 1 9
[ l o c a l ]
1 /
5
M i n u t e (
0 -
5 9 ) :
4 1
H o u r
(
0 -
2 3 ) :
2 2
D a y
(
1 -
3 1 ) :
1 2
M o n t h
(
1 -
1 2 ) :
2
Y e a r
(
1 9 9 0 -
2 0 8 9 ) :
1 9 9 8
Line 1 shows the current date, time and time synchronization source with which the internal
clock is synchronized. The time can be adjusted only when [Local] is indicated on the top line,
showing that the clock is running locally. When [IRIG] or [RSM] or [IEC] or [MOD] is
indicated, the following adjustment is invalid.
Enter a numerical value within the specified range for each item and press the
ENTER
key.
Press the
END
key to adjust the internal clock to the set hours without fractions and return
to the previous screen.
If a date which does not exist in the calendar is set and
END
is pressed, "Error: Incorrect date"
is displayed on the top line and the adjustment is discarded. Adjust again.
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......