Chapter 2 ’Installation and Startup’ — Mounting in Rack
18
ViBE EM4000 — Release 1.10
User Manual — 46073586AB02
Mounting in Rack
Rack mounting is not mandatory for ViBE EM4000 but the ventilation and
safety requirements given in this section must be observed in all cases.
ViBE EM4000 Installation Requirements
This section lists the principles to be observed and the steps to be taken
when installing ViBE EM4000 in a 19" rack.
Restrictions must be observed:
related to ventilation (see section
’Ventilation’
on page 18)
related to cabling (see
section
’Cabling’ on page 23
)
related to EMC ground (see
section
’EMC Ground’ on page 23
)
related to Power supply and protective ground (see
section
’Power
Supply and Protective Ground’ on page 24
).
Ventilation
Please note that product failure rates are increased by high
temperatures. The following precautions should therefore be observed:
Prevent hot air from one device being introduced into other devices.
Ensure adequate distribution of air flows to the device intakes.
Avoid the effects of natural convection between devices.
Avoid hot/cold air short-circuits.
Avoid transverse effects in coupled racks.
Prevent hot air from accumulating in the rack.
Check the air flows: the rack should ensure a sufficient supply of cold
air and sufficient evacuation of hot air (according to the number of
devices mounted in the rack and their corresponding air flows).
The following important requirements should be noted in addition to the
general recommendations:
The chassis must not be fixed with its rack mounting ears only. If you
intend to install it in a rack, L-profiles are required and you must
observe the ventilation and safety instructions described in the
following sections.
Summary of Contents for ViBE EM4000
Page 1: ...User Manual Release 1 10 ViBE EM4000 HD Encoder 46073586AB02 September 2012...
Page 4: ...4 ViBE EM4000 User Manual 46073586AB02 BLANK PAGE...
Page 12: ...Contents 12 ViBE EM4000 Release 1 10 User Manual 46073586AB02 Index 249...
Page 18: ...Preface Copyrights 6 ViBE EM4000 Release 1 10 User Manual 46073586AB02 BLANK PAGE...
Page 244: ...Alarms 232 ViBE EM4000 Release 1 10 User Manual 46073586AB02 BLANK PAGE...
Page 277: ...Alarm Help X733 syntax 9 60 103 Perte de temps r el Page 33...
Page 287: ...Alarm Help X733 syntax 9 60 105 Pas de ED dans le signal Page 43...
Page 292: ...Alarm Help X733 syntax 9 60 120 Pas de PCM dans le signal Page 48...
Page 303: ...Alarm Help X733 syntax 9 60 143 REMOTE FLEXTREAM Erreur de d bit PCR Page 59...
Page 324: ...Alarm Help X733 syntax 9 60 MTEP syntax alarms matching this probable cause french Page 80...