TI120 Series Variable Frequency Drive
Parameter List
- 62 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
P50.06
Master-slave
mode
selection and
slave function
code setting
ones: master-slave
selection for terminal port
communication
Tens: master-slave
selection for keyboard port
communication
0: stand-alone use
1: this machine is used as
the host
2: this machine is a slave
machine
Hundreds: operation
address of terminal port
communication
Thousands: communication
operation address of
extended port
0: P00.00
1: P40.01
0000
0x5006
●
P50.07
Interval time
of host
operation data
0.010s~1.000s
0.050s
0x5007
○
P50.08
Proportion
coefficient of
receiving date
of slave
machine
0.00~10.00
1.00
0x5008
○
P60 Motor Control Preparation
P60.00
Carrier
frequency
setting
≤ 15kW:1.0kHz~16.0kHz,
Factory value:6.0kHz
18.5kW-45kW:1.0kHz~10.0
kHz,
Factory value:4.0kHz
55kW-75kW:1.0kHz~8.0kH
z,
Factory value:3.0kHz
Model
determination
0x6000
●