TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 110 -
10V/20mA
P13.09
9
AI2 input
AI2 input 10V corresponds to
10V/20mA
AI2 input 10V corresponds to
P13.09
10
reserve
-
-
11
pulse input
100kHz corresponds to
10V/20mA
100kHz corresponds to P13.09
12
motor current
2 times of rated current of the
motor corresponding to
10V/20mA
2 times of rated current of the
motor corresponds to P13.09
13
output torque
(relative value)
2 times of rated torque of the
motor corresponds to 10V/20mA
2 times of rated torque of the
motor corresponds to P13.09
14
torque command
2 times of rated torque of the
motor corresponds to 10V/20mA
2 times of rated torque of the
motor corresponds to P13.09
P13.03
AO1 output bias
range: -100.0%~100.0%
Factory default:0.0%
P13.04
AO1 output gain
range: -2.000~2.000
Factory
default:1.000
P13.05
AO1 output filtering time
range:0.000s~10.000s
Factory
default:0.000s
P13.06
AO2 output bias
range: -100.0%~100.0%
Factory default:0.0%
P13.07
AO2 output gain
range: -2.000~2.000
Factory
default:1.000
P13.08
AO2 output filtering time
range: 0.000s~10.000s
Factory
default:0.000s
The default output is 0-10V or 0-20mA. If the range of the analog output is adjusted, it can be set
through the gain and offset of the above two groups of parameters; the following figure shows the typical
application settings of the industry.
y
x
0V/0mA
10V/20mA
Xmax
Gain 1.000, offset 0.0%
0V/0mA
10V/20mA
Xmax
Gain 0.800, offset 20.0%
2V/4mA
y
x