TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 84 -
P01.10
Selection of stop mode
range:0~1
Factory default:0
0: slow down and stop
The variable frequency drive receives the stop command and starts deceleration stopping
according to the setting deceleration time. In this stop mode, if the setting value of P01.13 is greater
than 0.00s, then it is decelerated and stopped firstly. When the output frequency is lower than the setting
value of P01.11, it starts to enter the stopping DC braking status and keeps the setting time of P01.12;
then it stops.
1: free stop
After receiving the stop command, the variable frequency drive immediately blocks the output, and
the motor stops freely stop according to the mechanical inertia.
P01.11
Starting frequency of stop DC
brake
range:0.00Hz~ upper limit
frequency
Factory
default:0.50Hz
P01.12
Stop DC brake current
range:0.0%~100.0%
Factory
default:50.0%
P01.13
Stop DC braking time
range:0.00s~30.00s
Factory
default:0.00s
Please refer to P01.10 for the detailed explanation of P01.11 and P01.13, and it is set as
deceleration stop mode.
P01.12 stopping DC braking current is a percentage relative to the rated current of the variable
frequency drive.
P02 acceleration and deceleration parameters
P02.00
Acceleration time 1
range:0.1s~3600.0s
Factory default:
Model determination
P02.01
Deceleration time 1
range:0.1s~3600.0s
Factory default:
Model determination
P02.02
Acceleration time 2
range:0.1s~3600.0s
Factory default:
Model determination
P02.03
Deceleration time 2
range:0.1s~3600.0s
Factory default:
Model determination
P02.04
Acceleration time 3
range:0.1s~3600.0s
Factory default:
Model determination