TI120 Series Variable Frequency Drive
Parameter List
- 52 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
P40.17
Deviation limit 0.0%~100.0%
0.0%
0x4011
○
P40.18
Differential
limit
0.0%~100.0%
0.5%
0x4012
○
P40.19
PID initial
value
0.0%~100.0%
0.0%
0x4013
○
P40.20
PID initial
value holding
time
0.0s~3600.0s
0.0s
0x4014
○
P40.21
PID operation
output
maximum
0.0%~100.0%
100.0%
0x4015
○
P40.22
PID reverse
output cutoff
frequency
0.00Hz~upper limit
frequency
0.00Hz
0x4016
○
P40.23
PID shutdown
operation
selection
0:no calculation during
shutdown
1:operation during
shutdown
0
0x4017
●
P40.24
PID given
missing
detection
value
0.0%~100.0%
0.0%
0x4018
●
P40.25
PID given loss
detection time
0.00s~30.00s
0.00s: not detect PID given
loss
1.00s
0x4019
●
P40.26
PID feedback
missing
detection
value
0.0%~100.0%
0.0%
0x401A
●
P40.27
PID feedback
loss detection
time
0.00s~30.00s
0.00s: not detect PID
feedback loss
1.00s
0x401B
●
P40.28
PID signal
loss shutdown
mode
0: free shutdown
1: emergency shutdown
0
0x401C
○