TI120 Series Variable Frequency Drive
Parameter List
- 34 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
P03.23
Power limit
coefficient in
power
generation
0.0%~200.0%
100.0%
0x0317
○
P03.24
Torque control
deviation
frequency
setting
0.00Hz~10.00Hz
0.00Hz
0x0318
○
P04 Scalar Control Parameters
P04.00
V/F curve
setting
0: straight line V/F
1: multi-stage V/F
2: 1.2 power
3: 1.4 power
4: 1.6 power
5: 1.8 power
6: 2.0 power
7: separation V/F
0
0x0400
●
P04.01
V/F frequency
value F0
0.00Hz~P04.03
0.00Hz
0x0401
●
P04.02
V/F voltage
value V0
0.0%~P04.04
0.0%
0x0402
●
P04.03
V/F frequency
value F1
P04.01~P04.05
0.00Hz
0x0403
●
P04.04
V/F voltage
value V1
P04.02~P04.06
0.0%
0x0404
●
P04.05
V/F frequency
value F2
P04.03~P04.07
0.00Hz
0x0405
●
P04.06
V/F voltage
value V2
P04.04~P04.08
0.0%
0x0406
●
P04.07
V/F frequency
value F3
P04.05~P63.03
50.00Hz
0x0407
●
P04.08
V/F voltage
value V3
P04.06~100.0%
100.0%
0x0408
●
P04.09
Torque boost
0.0%~30.0%
0.0%
0x0409
●