TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 82 -
source to facilitate the synchronous switching of run command and frequency source.
Ones: selection of keyboard command binding frequency source
0: digital given (P00.00)+Up/Down adjustment
1: analog input AI1
2: analog input AI2
3: reserve
4: Min[AI1,AI2]
5: Max[AI1,AI2]
6: Sub[AI1,AI2]
7: Add[AI1,AI2]
8: pulse given HDI
9: process PID
A: simple PLC
B: no given
Tens: selection of terminal command binding frequency source(Choose the same as above)
Hundreds: selection of communication command binding frequency source(Choose the same as
above)
For the description of the above frequency setting mode, please refer to P00.01 function code.
P01.02
Operation direction selection
range:0~1
Factory default:0
It is used for changing the rotating direction of the motor when the keyboard controls the run
command. Terminal control and communication control are not affected by this parameter.
0: positive direction
1: reverse direction
P01.03
Reverse control selection
range:0~1
Factory default:0
For some applications, the reverse rotation of the motor is not allowed, and the reverse rotation can
be prohibited by the function. When the rotating direction of the actual motor is opposite to the
equipment requirements, the positive direction of the equipment is consistent with the output of the
variable frequency drive by exchanging any two-phase wiring at the output side of the variable
frequency drive.
0: allow reverse rotation
1: forbid reverse rotation
P01.04
Positive and negative dead
time
range: 0.0s~3600.0s
Factory default:0.0s
It is used for defining the transition time of the variable frequency drive with 0.00Hz output
frequency when the variable frequency drive goes from forward to reverse or from reverse to forward.