TI120 Series Variable Frequency Drive
Parameter List
- 51 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
P40.08
Differential
time Td2
0.000s~50.000s
0.000s
0x4008
○
P40.09
PID
parameter
switching
selection
0: use Kp1, Ki1 and Kd1
only
1: automatically switch
according to input bias
2: switch according to
terminals
0
0x4009
●
P40.10
Input bias in
PID automatic
switching
0.0%~100.0%
20.0%
0x400A
○
P40.11
PID
adjustment
selection
Ones: output frequency
0: it must be consistent with
the set running direction
1: it can be opposite to the
set running direction
Tens: integral mode
0: when the integral
reaches the upper and
lower limits, continue to
adjust the integral.
1: when the integral
reaches the upper and
lower limits, stop the
integral adjustment.
11
0x400B
●
P40.12
PID positive
and negative
effects
0: positive effect
1: negative effect
0
0x400C
●
P40.13
PID given
filtering time
0.00s~10.00s
0.00s
0x400D
○
P40.14
PID feedback
filtering time
0.00s~10.00s
0.00s
0x400E
○
P40.15
PID output
filtering time
0.00s~10.00s
0.00s
0x400F
○
P40.16
Sampling
period
0.001s~50.000s
0.002s
0x4010
○