TI120 Series Variable Frequency Drive
Parameter List
- 37 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
P10.15
X1 terminal
disconnection
delay
0.0s~3600.0s
0.0s
0x100F
○
P10.16
X2terminal
conduction
delay
0.0s~3600.0s
0.0s
0x1010
○
P10.17
X2 terminal
disconnection
delay
0.0s~3600.0s
0.0s
0x1011
○
P10.18
Terminal
detection
mode
Ones: Bit0
~
Bit3:X1~X4
Tens: Bit4
~
Bit6:X5~X7
Hundreds: Bit8
~
Bit9:AI1~AI2
0: level valid
1: edge valid
000
0x1012
●
P11 switching value Y/R output
P11.00
Y1 terminal
function
selection
00: no output
01: variable frequency drive
in operation
02: forward running of
variable frequency drive
03: reverse running of
variable frequency drive
04: ready to complete of
variable frequency drive
05: variable frequency drive
in zero frequency operation
(stop ON)
06: variable frequency drive
in zero frequency operation
(stop OFF)
07: frequency reaching FAR
08: frequency level
detection signal FDT1
09: frequency level
detection signal FDT2
10: frequency upper limit
11: frequency lower limit
12: torque limiting action
(during speed control)
13: speed limiting action
(during torque control)
14: X1 terminal status
15: X2 terminal status
16: zero current detection
17: DC braking of variable
frequency drive
18: variable frequency drive
under-voltage
19: variable frequency drive
fault output
20: variable frequency drive
alarm output
21: variable frequency drive
overload early warning
22: variable frequency drive
overheating alarm
23: motor overload early
warning
24: motor overheating
alarm
25: PLC cycle completed
26: PLC stage completed
27: reserve
28: reaching cumulative
power-on time
29: reaching cumulative
running time
30: reaching the setting
count value
31: reaching the specified
count value
32: reaching the setting
length
33: Brake control output
(only for crane type)
0
0x1100
●
P11.01
Y2 terminal
function
selection
0
0x1101
●
P11.02
R1 relay
function
selection
0
0x1102
●
P11.03
R2 relay
function
selection
19
0x1103
●