TI120 Series Variable Frequency Drive
Parameter List
- 35 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
0.0%: effective automatic
torque promotion
P04.10
Droop control
quantity
0.00Hz~10.00Hz
0.00Hz
0x040A
●
P04.11
V/F oscillation
suppression
gain 1
0~1024
160
0x040B
○
P04.12
V/F oscillation
suppression
gain 2
0~1024
160
0x040C
○
P04.13
V/F
separation
mode voltage
given
selection
0: P04.14 digital setting
1: analog input AI1
2: analog input AI2
3: reserve
4: process PID output
5: process PID AI1
0
0x040D
●
P04.14
V/F
separation
mode voltage
digital given
0.0%~100.0%
0.0%
0x040E
○
P04.15
V/F
separation
mode voltage
change time
0.00s~600.00s
0.01s
0x040F
○
P10 switching value x input
P10.00
X1 terminal
function
selection
00: no function
01: forward running (FWD)
02: reverse running (REV)
03: forward running inching
(FJOG)
04: reverse inching (RJOG)
05: 3-wire operation
06: free stop
07: emergency stop
08: external stop
09: operation forbidden
10: operation suspended
11: external fault input
12: fault reset (RESET)
13: terminal adjustment Up
14: terminal adjustment
Down
15: Up/Down setting
clearing (terminal,
keyboard)
16: multi-stage frequency
terminal 1
17: multi-stage frequency
terminal 2
18: multi-stage frequency
terminal 3
19: multi-stage frequency
terminal 4
20: selection of acceleration
and deceleration time 1
21: selection of acceleration
and deceleration time 2
22: acceleration and
deceleration forbidding
23: command switch to
keyboard control
24: command switch to
terminal control
25: command switch to
communication control
26: frequency source
switching (P00.06[ ones])
27: main frequency source
switch to frequency digital
setting
28: auxiliary frequency
source Switch to frequency
digital setting
29: stop DC stop
command
30: stop DC braking
31: running DC braking
32: pulse input (X7/HDI
support high speed)
33: count input
34: count clearing
35: length counting
36: length clearing
37: PID action direction
38: PID parameter
switching
39: PID operation
suspending
40: PID integral suspending
41: PLC memory clear
42: PLC operation failure
43: PLC operation
suspending
44-45: reserve
46: speed/torque switching
47: torque control
forbidding
1
0x1000
●
P10.01
X2 terminal
function
selection
2
0x1001
●
P10.02
X3 terminal
function
selection
16
0x1002
●