TI120 Series Variable Frequency Drive
Parameter List
- 47 -
Parameter
Name
Setting range
Factory
default
Register address
Properties
variable
frequency
drive overload
pre-alarm
detection
detection selection
0: always check during
operation
1: detection at constant
speed operation only
Tens: selection of overload
pre-alarm detection
quantity
0: detection level is relative
to rated current of motor
1: detection level is relative
to rated current of variable
frequency drive
Hundreds: Overload
pre-alarm protection
selection
0: overload protection
shield
1: overload protection
enabled
P30.04
Detection
level of
variable
frequency
drive overload
pre-alarm
20.0%~200.0%
160.0%
0x3004
●
P30.05
Detection time
of variable
frequency
drive overload
pre-alarm
0.0s~60.0s
5.0s
0x3005
●
P30.06
Output load
drop detection
selection of
variable
frequency
drive
0: invalid detection of
output load drop of variable
frequency drive
1: always check during
operation (continue
operation)
2: detection only at
0
0x3006
●