Section 6 – SR-2 Service Procedure D01A
Control and Display Return Air Sensors
These sensors
monitor the temperature of the air returning to the evaporator coil. The sensors are located in the
return air flow and are connected directly to the microprocessor connector J3. These sensors are graded sensors
and must be replaced with graded sensors. The microprocessor must be calibrated to the respective grade of the
installed sensor in order to operate properly. The Control Return Air Sensor is marked with one yellow cable tie
and is connected to the microprocessor via the RTP and RTN wires. The Display Return Air Sensor is marked
with two yellow cable ties and is connected to the microprocessor via the RTRP and RTRN wires. When
replacing a sensor, be certain the sensors are connected properly.
Control and Display Discharge Air Sensors
These sensors monitor the temperature of the air leaving the evaporator coil. The sensors are located in the
evaporator discharge air path and are connected directly to the microprocessor via connector J3. These sensors
are graded sensors and must be replaced with graded sensors. The microprocessor must be calibrated to the
respective grade of the installed sensor, in order to operate properly. The Control Discharge Air Sensor is
marked with one red cable tie and is connected to the microprocessor via the DTP and DTN wires. The Display
Discharge Air Sensor is marked with two red cable ties and is connected to the microprocessor via the DTRP and
DTRN wires. When replacing a sensor, be certain the sensors are connected properly.
Hard and Soft Failures
Sensor alarms can occur in the following ways.
A
“Hard Failure”
is defined by an out of range sensor reading, typically caused by an open or shorted sensor.
The sensor display will show dashes if a hard failure occurs. If this occurs only the alarm code for that sensor will
be set. Alarm code 13 will not be present. The controller may not be showing dashes for the sensor reading, but
the alarm will be active when the unit is inspected. If a sensor alarm code is set, a failure did occur at some point.
Checking a ServiceWatch data logger download at Technician Level may indicate when the hard failure occurred.
A
“Soft Failure”
is defined by erratic operation or sensor drift that exceeds acceptable tolerances, (sensor is out
of calibration). If this occurs the alarm code for the suspect sensor or sensors will be set along with Alarm Code
13. This indicates a potential problem that may not be immediately apparent, and that a hard failure as defined
above did not occur. Checking a ServiceWatch data logger download at Technician Level may indicate when
the soft failure occurred.
Page 2
P41RD01A 01 February 2005
Summary of Contents for SR-2 SmartReefer2
Page 4: ......
Page 7: ...Tab goes here and the next page should be GREEN Section 1 Safety...
Page 8: ......
Page 10: ...Section 1 SR 2 Safety Information 1 2 18 January 2005...
Page 14: ...Section 1 SR 2 Safety Information 1 6 18 January 2005...
Page 15: ...Tab goes here and the next page should be GREEN Section 2 Hardware Description...
Page 16: ......
Page 48: ...Section 2 SR 2 Hardware Description 2 32 31 January 2005...
Page 49: ...Tab goes here and the next 2 pages should be GREEN Section 3 Software Description...
Page 50: ......
Page 96: ...Section 3 SR 2 Software Description 3 46 31 January 2005...
Page 97: ...Tab goes here and the next page should be GREEN Section 4 Operation...
Page 98: ......
Page 181: ...Tab goes here and the next 2 pages should be GREEN Section 5 Diagnostics...
Page 182: ......
Page 266: ...Section 5 SR 2 Diagnostics 5 84 02 February 2005...
Page 267: ...Tab goes here and the next page should be GREEN Section 6 Service Procedures...
Page 268: ......
Page 270: ...Section 6 SR 2 Service Procedure Index Page 2 01 February 2005...
Page 282: ...Section 6 SR 2 Service Procedure A01B Page 6 P41RA01B 31 January 2005...
Page 298: ...Section 6 SR 2 Service Procedure A02A Page 12 P41RA02A 02 February 2005...
Page 318: ...Section 6 SR 2 Service Procedure A03B Page 4 P41RA03B 30 January 2005...
Page 338: ...Section 6 SR 2 Service Procedure A15A Page 4 P41RA15A 30 January 2005...
Page 360: ...Section 6 SR 2 Service Procedure A46B Page 8 P41RA46B 30 January 2005...
Page 366: ...Section 6 SR 2 Service Procedure A48A Page 6 P41RA48A 30 January 2005...
Page 376: ...Section 6 SR 2 Service Procedure A50A Page 6 P41RA50A 31 January 2005...
Page 394: ...Section 6 SR 2 Service Procedure F08A Page 4 P41RF08A 30 January 2005...
Page 398: ...Section 6 SR 2 Service Procedure F09A Page 4 P41RF09A 30 January 2005...
Page 402: ...Section 6 SR 2 Service Procedure G03A Page 4 P41RG03A 31 January 2005...
Page 406: ...Section 6 SR 2 Service Procedure H04A Page 4 P41RH04A 30 January 2005...
Page 407: ...Tab goes here and the next page should be GREEN Section 7 Service Information...
Page 408: ......
Page 410: ...Section 7 SR 2 Information 7 2 02 February 2005...
Page 419: ...Tab goes here and the next page should be GREEN Section 8 Schematics and Wiring Diagrams...
Page 420: ......
Page 422: ...Section 8 SR 2 Drawings 8 2 01 February 2005...
Page 424: ...Section 8 SR 2 Drawings 8 4 01 February 2005...
Page 425: ...8 5...
Page 426: ...8 6...
Page 427: ...8 7...
Page 428: ...8 8...
Page 429: ...8 9...
Page 430: ...8 10...
Page 431: ...8 11...